logo


Measuring common mode current

This article describes an instrument for measuring common mode current in a ham station HF antenna system.

Objectives

Design

The nature of common mode current

Common mode current is a component of current flowing on an RF transmission line. It is a component of each line current in the case of two wire open line, and in the case of a coaxial line, it flows entirely and exclusively on the outer surface of the outer conductor.

In both cases, common mode current forms a standing wave on the transmission line, it varies in amplitude and phase along the line.

Because it forms a standing wave, measurement at a single point does not guarantee that a significant current will be observed even though there is significant common mode current, you may just be measuring at or near a current minimum.

Is a current minimum at the shack as good as no current? No, not at all because associated with a current minimum is a voltage maximum, very high electric field intensity exists in the region of a voltage maximum (or current minimum). This is what gives rise to RF burns to the lips from microphone grilles!

An approach to measurement

Common mode current can be measured for either coaxial or two wire open line by making a current transformer comprising the transmission line conductors as the primary and a secondary winding with low resistance load and a half wave detector driving a high impedance voltmeter.

A simple half wave detector with Germanium diode was chosen as having excellent sensitivity and least compression of the scale at low input levels.

Sensitivity

In practical application, the instrument is likely to be used to assess common mode current in a situation where an common mode choke has been employed. Common mode chokes range in impedance, typically about an average resistance component of around 1000Ω. If such a choke could safely continuously dissipate say 10W due to common mode current, that current would be (P/R)^0.5=(10/1000)^0.5=0.1A RMS.

An instrument designed for Full Scale Deflection (FSD) of 0.1A RMS will have sufficient sensitivity to read upscale on currents that become an issue for typical common mode chokes. In practice, transmitter power would be reduced to minimum, and raised only sufficiently to obtain useful deflection. Common mode current measurements do not need to be made at maximum power out.

An option is offered for an additional switched range of 1A RMS FSD.

Calibration / scaling

The scale on a simple half wave rectifier with capacitor filter is close to linear for input voltages that are much greater than the diode nominal forward voltage drop, but no so at lower voltages.

To achieve the desired sensitivity, this instrument will have a non linear meter scale. The FSD input voltage, source impedance to some extent, and all of the detector components affect the scale shape. The main factors are the FSD input voltage, diode characteristics, capacitor and load resistance.

Fig 1: LTSPICE model

A SPICE model of the detector is useful in demonstrating circuit behaviour. Above is the detector circuit after the current transformer modelled in LTSPICE. The current source is equivalent to 100mA RMS input current via a 1:10 ratio current transformer, R2 represents a 50µA  FSD moving coil meter and sufficient resistance to obtain full scale deflection with 100mA input to the instrument. In practice, R2 includes a pot that allows calibration of FSD with 100mA RMS of input current.

Fig 2: LTSPICE model results

Above, the LTSPICE waveforms with current drive of 10mA RMS, shown after the circuit settles. The green line is the RF voltage into the detector, the blue line is the output voltage, and the red line is the diode current.

We might expect the RF voltage across the 100Ω resistor (the green line) to peak at 10e-3*100*2^0.5=1.414V, but it is a little lower at 1.356V due to the loading effect of the detector circuit.

Diodes are often thought of using a very simple idealised model that current flows when they are forward biased, and it doesn't flow when they are reverse biased. The red line shows that at small signals, the behaviour is not so simple.

The voltage drop across the diode is the difference betwen the green line and the blue line. It can be seen that as the green line increases above the blue line, diode current increases slowly at first, but more rapidly once the voltage drop exceeds about 150mV, decreasing again as the voltage drop falls to zero.

Note that the diode current doesn't just fall to zero, but is actually negative roughly until the green line reaches its negative peak. This is caused mainly by the diode's self capacitance. The peak diode current is 550µA, the average (DC) current is 50µA, and the RMS current is 140µA.

The effect of the current waveform over time is that the C1 acquires charge and reaches an average voltage (there is a little ripple which cannot be seen on the graph) of 1.086V. R2 is adjusted so that the average (DC) current in the meter (part of R2 here) is 50µA.

At lower input voltage, the current waveform is less peaky, and the output voltage is smaller in relation to the input voltage.

The higher range of 1A FSD is almost linear down 0.1A.

Prototype

Scaling

A prototype was constructed and output measured for input at 10MHz from 0.1V to 1V, and the DC output recorded.

Fig 3: Block diagram of detector measurement setup

Above is a block diagram of the detector measurement setup. The computer controls the instruments via the GPIB bus, setting the HP8658B SSG power level and frequency, and measuring the detector output using the DVM option in the HP5328A.


Table 1:
Ip
(% of FSD)
Deflection
(% of FSD)
10 2.5
20 10.6
30 20.9
40 31.8
50 43.0
60 54.3
70 65.7
80 77.0
90 88.6
100 100.0

The table above shows the deflection vs primary current for the 100mA range. The 1A range is taken to be linear.

The prototype was calibrated by measuring the current with a 7MHz transmitter adjusted to 50W and 0.5W (using a 20dB power attenuator) into a 50Ω dummy load.

In the prototype, the DC voltage developed in the load at 1A is 12.2V, and at 0.1A is 0.94V. This requires nominal load resistance of 244k and 19.2k respectively. In the prototype, the high range uses a 220kΩ fixed in series with a 50kΩ pot and the low range a 15kΩ fixed in series with a 5kΩ pot, with a single pole double throw switch to select high/low range.

Fig 4:

Above is a plot of the frequency response of the low range detector over HF.

Fig 5:

Above is an illustration of the scaling, it is scale plate artwork for a common MU-45 size 50µA meter. The artwork is available for download. (You may notice from the artwork that it was created with Tonne Sofware's Meter program. This is the ONLY piece of software that I have ever purchased that cluttered the printed output with its own promotional message, so to give balance, for that and many other reasons, it is without doubt the worst piece of software for which I have ever paid money, I do not recommend it.)

Transformer

The transformer used on the prototype is a Fair-rite 0443164151 snap on suppression sleeve large enough to go over RG213 sized cable with the secondary winding in place.

Fig 6: Fair-rite 0443164151

Above, the snap on suppression sleeve. Dimension B of the 0443164151 is 13.5mm.

Fig 7: Veroboard copper side
 

Above, the copper side of the veroboard. Eagle eyes will see there is a track broken where it should not have been and is bridged with the pigtail of a resistor... don't copy my mistake!



Fig 8: Meter interior
 

Above, the meter interior. The 100Ω resistor used is a carbon film 1W rated device, so the meter's continuous current rating is I=(P/R)^0.5/n=(1/100)^0.5/0.1=1A.

Fig 9: The RF current meter

Above, the meter ready for use.

Construction hints

The prototype used a commercial snap on balun. Though the hinge is likely to fail with repeated use, it provides a good prototype instrument. The core is fixed to the plastic box using double sided foam tape, and then the secondary winding of ten turns of 0.5mm ECW wound tightly around both the core unit and plastic case via two 3mm diameter holes.

Whilst the meter would usually be supported by the cable being measured in practice, provision is made for hand holding the instrument at the end opposite the transformer where there is no internal circuitry, and isolation will be quite good.

Applying  the meter

Although the meter only measures the magnitude of current, by making three measurements, the magnitude of the differential and common mode components and the magnitude of their phase relationships can be determined.

Measure:

Note that I12 must not be greater than I1+I2, if it is, then the measurements are in error.

I1 (A)
I2 (A)
I12 (A)
 
Ic  (A)
Id  (A)
θdc  (°)
θ12 (°)

The above form allows calculation of Ic  (the common mode component of current), Idc (the differential mode component of current), θdc (the magnitude of phase difference of Id wrt Ic, θ12 (the magnitude of phase difference of I2 wrt I1). (The instrument does of course directly read Ic as I12.)

Note that external fields are principally due to 2Ic (or measured I12).

The calculator tries to use the number entered, negative numbers will be changed to positive, missing data 0, NaN means Not A Number (correct the input if needed), results will not be calculated when I12 > I1+I2.

The low meter range is the most useful range, as meaningful readings can be made at relatively low power. Keep in mind that Ic=0.1A flowing in each conductor in a common mode choke with an R component of Z (the effective RF resistance of the choke) of say 1000Ω means (2*0.1)^2*1000=40W of dissipation in the choke.

A case study

A correspondent described failure of a balun on his G5RV though arcing at 800W output on 40m.

Fig 10: Damaged current balun

Above left is a section of the balun winding that had arced and burned the covering PTFE insulation.

The balun is a 1:1 Guanella balun, "W2FMI type" rated at 5kW continuous, 10kW peak. The conductors were specified by the manufacturer as 200°C magnet wire, and they appear to have been wrapped with PTFE tape.

A G5RV on 40m will drive a VSWR of about 10:1 on 400Ω line, so at 800W for example, the worst case differential voltage will be (2*800*400*10)=2500Vpk. Evidently the balun insulation was not sufficient to withstand the applied differential operating voltage at 800W in this case, less than 10% of the manufacturer's peak power rating.

Fig 11: The rewound balun

To better understand what was happening, the correspondent replaced the faulty winding with one of a twisted pair of PTFE insulated flexible wires, wound in exactly the same configuration as the original. Fig 11 shows the rewound balun.

Having rewound the balun, it now withstood the operating voltage without flashoveer, but the correspondent experienced serious overheating within a minute using just 800W tx output on a G5RV at 40m. Some other bands had the same problem, some not.

He constructed a similar clip on current meter, and  measured I1=0.4A, I2=0.39A and I12=0.1A in the open wire feeder adjacent to the balun at 50W tx output.

Using the calculator, Ic is just 12% of Id which would be regarded by many as insignificant, yet the balun had been destroyed and needed to be rewound, and even after rewind (which had not solved the underlying problem), behaved badly at more than about 50W (notwithstanding that it was rated at 5kW).

If the R component of Z of the balun was say 1000Ω at 7MHz, then the power dissipated in the core would be 0.1^2*1000=10W, or 20% of the 50W tx output. Ten Watts might not seem much, but when the transmitter was operated at 800W, that would be 160W which increased the core to its Curie temperature withing seconds, rendering it ineffective as a choke and damaging insulation materials.

Total common mode current of 0.1A might not seem much, but it is enough current to drive very high losses in a medium impedance common mode choke (balun). The answer is to reduce the current further, even if increasing the choke R, until I^2R is within the choke's acceptable dissipation.

Some messages to take away are:

Fig 11: Better winding configuration

A better winding configuration is for this balun is the W1JR "cross over' configuration as shown in Fig 12. The winding provides for input and output on opposide sides of the core, whilst spreading the turns out to minimise self capacitance.

Instruments that do not reliably indicate balance

There have been a number of designs that purport to indicate transmission line current balance. Current balance means that the line currents at a point are of exactly equal magnitude but exactly oppoiste phase.

Two examples of flawed designs that compare magnitude but not phase follow.

Such instruments reliably show unbalance, but they do not reliably show balance (equal magnitude currents is not sufficient to prove balance). The first of these links is to a product current in MFJ's catalogue at Jul 2011, and the second is to an article online at the same date and appearing in print in AR magazine in August 2009.

Try entering 1, 1 and 2 A in the calculator above. Both line currents are equal in magnitude at 1A, but the common mode current is 2A and this represents the worst imbalance, even though both line currents have equal magnitude. Both instrments mentioned would indicate perfect balance.

Links

Changes

Version Date Description
1.01 30/05/2011 Initial.
1.02    
1.03    
1.04    
1.05    

VK1OD on the 'net. I appreciate feedback, click on the ... in webm...@vk1od.net for my email address.

© Copyright: Owen Duffy 1995, 2011. All rights reserved. Disclaimer.